AHU-FC04 · Air-side AHU · ASHRAE Guideline 36 FC04

Operating state hunting

The AHU is flipping between heating, free cooling, and mechanical cooling many times an hour.

Capacity-basedBAS trendsGuideline 36Medium effort

What does AHU-FC04 mean?

The AHU is flipping between heating, free cooling, and mechanical cooling many times an hour.

Why does it matter?

Every state change is a transient: coils fill and drain, dampers stroke, the supply temperature overshoots. It wastes energy and wears actuators, and it usually means the sequence has no deadband between modes.

What should you do?

Add or widen the deadbands between heating, economizer, and cooling in the AHU sequence; check the SAT setpoint reset and the mixed-air low-limit; verify the OAT sensor isn't noisy.

How Energy Agent prices a finding

Written by Pelorus Engineering · Brent Waluzak, P.E. (FL), President, Pelorus EngineeringLast updated

Screening-level estimates; confirm with measurement and verification before capital commitment.