Fault family · 18 rules

Central plant faults

Chillers, boilers, towers and pumps.

Eighteen rules for the central plant: low chilled-water and hot-water ΔT, condenser and tower approach drift, short-cycling, chillers idling at low load, missing supply-temperature and pressure resets, decoupler reverse flow and condensing boilers that never condense. Plant faults are fewer than air-side faults but each one is usually worth more.

How to read it. Three days at the chiller. Blue is the chilled water leaving the chiller, teal is the water coming back. The gap between them (the ΔT) should stay wide when the plant is loaded. Here it narrows day by day; the red area marks where it has collapsed, which means pumps are moving far more water than the load needs.

Low chilled-water delta-T: the loop moves more water than the load needs45505560Day 1Day 2Day 3°Fchilled-water returnchilled-water supplyΔT collapsing at full load
supply temperaturereturn temperaturedelta-T below design
Illustrative synthetic data, not a customer trend.

The rules

Estimate it

What is low ΔT costing in pumping?

Estimate the extra pump energy from moving more water than the load needs.

Enter a repair or controls-change cost to see the simple payback.
Avoidable cost per year—Energy —Simple payback Enter a cost to fix to see the payback.

    Pump power rises with the cube of flow. At design ΔT the loop needs only (actual ÷ design) of today’s flow, so pump power at design would be that ratio cubed. Energy Agent measures ΔT and pump power from the plant trends.

    Screening estimate. Energy Agent measures the real fault hours and load from your trends and prices them at your tariff.

    Your first building is free.

    Send twelve months of interval data, a BAS trend export, or just the bills. You get a screening-level report of what the building is wasting, what that is worth at your tariff, and what to do first. One building per organisation, no sensors, no installation, no commitment.