Energy Agent · Fault library

The faults that waste energy in commercial buildings, one page each.

Energy Agent runs 96 fault-detection rules over the meter and BAS data your building already produces. This library explains what each fault means, why it costs you money or comfort, and what to do about it.

96rules
8equipment families
16Guideline 36 conditions
17diagnostic rules

What a rule page gives you

  1. What it means. The physical situation the rule has found, in plain terms: which equipment, which condition, and over what kind of period.
  2. Why it matters. What the fault costs — energy, demand, comfort, equipment life — and why it tends to go unnoticed.
  3. What to do. Where to look first and the usual fixes, ordered from the cheapest and most common cause outward.

The sixteen AHU-FC rules are aligned with the fault conditions FC01–FC16 described in ASHRAE Guideline 36. The logic is expressed in Pelorus Engineering’s own engineering terms; Guideline 36 text is not reproduced here.

The map

Which data unlocks which rules

Every dot on the ring is one of the rules, grouped by equipment. Inside are the kinds of data point they need. Point at a data point to see every rule it feeds, or at a rule to see what it needs.

96 rules, 62 kinds of data point, 222 connections. Point at anything.

Cooling valve commandDuct static pressureDuct static pressure setpointSupply fan status or speedHeating valve commandMixed-air temperatureOutside-air damper commandReturn-air temperatureSupply-air temperatureSupply-air temperature setpointBuilding static pressureBoiler statusChiller powerChiller statusChilled-water return temperatureChilled-water supply setpointChilled-water supply temperatureCondenser-water entering temperatureCondenser-water leaving temperatureCondenser-water setpointDOAS supply-air temperatureDOAS supply-air setpointExhaust fan statusEnergy-recovery bypass damperEnergy-recovery air temperaturesDischarge-air temperatureFan statusValve command (cooling and heating)Zone temperaturePrimary and secondary loop flowInterval gas dataAuxiliary heat statusCompressor statusDefrost statusHeating or cooling modeReturn-air temperatureSupply-air temperatureHot-water return temperatureHot-water supply temperatureLighting circuit submeterInterval electricity, main meterOutdoor-air temperaturePump differential-pressure setpointPump status or speedCompressor or cooling-stage statusSupply fan statusHeating-stage statusOutside-air damper commandSupply-air temperatureOccupancy scheduleCooling-tower fan status or speedAirflow and airflow setpointDamper positionReheat valve commandCooling and heating setpointsZone temperatureIndoor unit status and mode (two or more units)Zone CO₂Zone relative humidityOccupied and unoccupied setpointsZone temperature (any zone)Zone temperatures for three or more zonesMET-01 Excessive night / weekend baseloadMET-02 Baseload creeping up over timeMET-03 After-hours operationMET-04 Weekend load shape looks like a weekdayMET-05 Anomalous peak demand eventMET-06 Weather sensitivity has changedMET-07 Heating + cooling fuel signature overlapMET-08 Anomalous daily load shapeMET-09 Sudden step change in baselineMET-10 Meter data integrity issueMET-11 Lighting on after hoursAHU-FC01 Duct static pressure cannot be metAHU-FC02 Mixed-air temperature below both OAT and RATAHU-FC02/03/06 Mixed-air temperature doesn't match OA/RA mixAHU-FC03 Mixed-air temperature above both OAT and RATAHU-FC04 Operating state huntingAHU-FC05 Supply air not warming across active heatingAHU-FC06 OA fraction wrong for current operating stateAHU-FC07 SAT low while heating valve is full openAHU-FC08 SAT and MAT not tracking in economizerAHU-FC09 OAT too high for SAT setpoint with free cooling aloneAHU-FC10 Mixed air not tracking outdoor air at 100% OAAHU-FC11 Mechanical cooling with outdoor air cold enough to do the jobAHU-FC12 SAT too high relative to MAT in cooling modeAHU-FC13 Supply air too warm with the cooling valve full openAHU-FC14 Temperature drop across inactive cooling coilAHU-FC15 Temperature rise across inactive heating coilAHU-X01 Fighting coils — heating and cooling on at the same timeAHU-X02 Reheat clawing back overcooled airAHU-X03 Fan power deviates from fan-curve expectationAHU-X04 SAT setpoint is constant — no reset strategyAHU-X05 Equipment running outside its occupancy scheduleAHU-X06 Control loop oscillatingAHU-X07 Sensor value frozenAHU-X08 Valve pegged open or closedAHU-X09 Supply fan riding high with no cooling demandAHU-X10 Hot-water supply not following OAT resetAHU-X11 Supply air temperature missing setpointAHU-X12 Reheat active during unoccupied hoursAHU-X13 Outside-air damper open past minimum without economizer reasonAHU-X14 Mechanical cooling while free cooling was availableAHU-X15 Static-pressure setpoint never resetsERV-FC16 Energy recovery not recoveringVAV-01 VAV airflow sensor miscalibratedVAV-02 VAV damper leaking when commanded closedVAV-03 VAV reheat valve leakingVAV-04 Zone outside its setpoint bandVAV-05 VAV reheat valve pegged but zone still coldVAV-06 VAV box stuck at min or max airflowVAV-07 Single zone driving AHU resetFCU-01 Fan-coil valve leaking byFCU-02 Fan-coil fan out of step with its callFCU-03 Four-pipe fan-coil heating and cooling togetherZONE-01 Over-ventilating a lightly occupied zoneZONE-02 Under-ventilated zone (CO₂ high)ZONE-03 Zone humidity out of bandZONE-04 Condensation risk on a chilled surfaceZONE-05 Zone temperature sensor biased vs neighboursZONE-06 Occupied setpoints outside policyZONE-07 Night setback too shallowPLANT-01 Chiller can't make chilled-water supply setpointPLANT-02 Low chilled-water ΔT syndromePLANT-03 Condenser approach drifting up — likely tube foulingPLANT-04 Boiler and chiller running at the same timePLANT-05 Pump running with no flowPLANT-06 Cooling-tower fan short-cyclingPLANT-07 Chiller short-cyclingPLANT-07B Boiler short-cyclingPLANT-07D Chiller efficiency driftingPLANT-08 Chiller running at very low loadPLANT-09 Chilled-water supply reset absentPLANT-10 Condenser-water reset absentPLANT-11 Cooling-tower approach highPLANT-12 Tower fans overshooting setpointPLANT-13 Decoupler reverse flowPLANT-14 Condensing boiler not condensingPLANT-15 Hot-water loop low ΔTPLANT-16 Pump ΔP reset absentRTU-01 Compressor short-cyclingRTU-02 Cooling / heating stage huntingRTU-03 DX cooling capacity degradedRTU-04 Integrated economizer not usedRTU-05 Heat and cool stages on togetherRTU-06 Supply fan running after hours with no callRTU-07 High compressor runtime on cool daysHP-01 Auxiliary heat without lockoutHP-02 Excessive defrostHP-03 Heat-pump compressor short-cyclingHP-04 Reversing valve / mode mismatchVRF-01 VRF indoor units in conflicting modesVRF-02 VRF indoor unit runtime imbalanceBP-01 Building pressure out of bandDOAS-01 DOAS supply setpoint not metEF-01 Exhaust running without supplyEF-02 Exhaust running outside the scheduleERV-02 Energy-recovery bypass open when recovery pays
  • Whole-building meter · 11
  • Air-side AHU · 32
  • VAV / zone · 7
  • Zones & IAQ · 10
  • Central plant · 18
  • Packaged RTU / DX · 7
  • Heat pumps / VRF · 6
  • DOAS / ERV / exhaust · 5
a rule (click for its page)a rule you can watch in a 3D modela kind of data point; bigger feeds more rules

The readiness quiz scores your own building against the same table.

Reading a rule page

How to read a rule

Every rule page has the same three sections, written for the person who has to act on it rather than the person who wrote the detector.

The pricing badge

Each rule carries a pricing badge. Physics-based rules use a rule-specific model of the wasted energy. Capacity-based rules combine the equipment’s capacity, its duty and the fault hours. Meter rules are priced directly from the excess the meter recorded. The method is stated on every finding in Energy Agent, never hidden. After a fix, the saving is verified against the meter: see how savings are verified.

Diagnostic rules claim no dollars

Diagnostic rules claim no dollars at all, by design. A biased sensor, an under-ventilated classroom or a boiler that cannot hold setpoint is still surfaced and ranked, but as a comfort, reliability or data-quality problem — never inflated into savings.

Faults cascade

When an upstream delivery problem explains a downstream symptom over most of the same hours, the symptom is folded into its cause so one root cause is not counted several times. The hidden dollars still appear on the cause.

A data-quality gate runs first

Before any rule runs, a data-quality gate checks the supplied trends — gaps, frozen channels, unit mismatches, timestamp problems — and decides which analyses the data can actually support. A rule that cannot be trusted on your data is not run.

What this library does not show

This library describes the faults, not the detectors. Thresholds, tolerances and timing windows are tuned per building inside Energy Agent and are not published here.

Index

All 96 rules

Search by code, equipment or symptom, or narrow by family and pricing. Every rule links to its own page.

Your first building is free.

Send twelve months of interval data, a BAS trend export, or just the bills. You get a screening-level report of what the building is wasting, what that is worth at your tariff, and what to do first. One building per organisation, no sensors, no installation, no commitment.