AHU-X04 · Air-side AHU

SAT setpoint is constant — no reset strategy

The supply-air-temp setpoint never moves across the analysis window, indicating no trim-and-reset or load-based reset is happening.

Capacity-basedBAS trendsMedium effortNeeds schedule

What does AHU-X04 mean?

The supply-air-temp setpoint never moves across the analysis window, indicating no trim-and-reset or load-based reset is happening.

Why does it matter?

A static SAT setpoint forces VAV boxes to reheat at low loads (excess cooling) or strain at high loads. ASHRAE 90.1 requires SAT reset on most multi-zone AHUs for this reason. Often a 15–20% AHU energy reduction is left on the table.

What should you do?

Implement trim-and-reset based on the most-open VAV box, or a simple OAT-based reset. Confirm the BMS reset logic actually has authority over the SAT setpoint.

See it happen · interactive 3DSwitch AHU-X04 on in the interactive 3D air handlerOpens the air handler on this fault: watch the dampers, the coils, the boxes and the bill change.

How Energy Agent prices a finding

Written by Pelorus Engineering · Brent Waluzak, P.E. (FL), President, Pelorus EngineeringLast updated

Screening-level estimates; confirm with measurement and verification before capital commitment.