DOAS-01 · DOAS / ERV / exhaust

DOAS supply setpoint not met

The dedicated outdoor-air unit's supply temperature misses its setpoint for an hour or more while running.

Diagnostic · comfortBAS trendsMedium effort

What does DOAS-01 mean?

The dedicated outdoor-air unit's supply temperature misses its setpoint for an hour or more while running.

Why does it matter?

The terminal units downstream inherit a latent and sensible load they were never sized for — humidity complaints and lost capacity.

What should you do?

Check coil capacity and chilled-water availability, the reset schedule, the wheel/recovery section and the sensor location.

This is a diagnostic rule: Energy Agent surfaces and ranks it as a comfort problem and claims no dollar savings for it, by design.

See it happen · interactive 3DSwitch DOAS-01 on in the interactive 3D hotelOpens the hotel on this fault: watch the rooms, the roof, the pressure and the bill change.

How Energy Agent prices a finding

Written by Pelorus Engineering · Brent Waluzak, P.E. (FL), President, Pelorus EngineeringLast updated

Screening-level estimates; confirm with measurement and verification before capital commitment.