What does AHU-FC10 mean?
With the outdoor-air damper fully open, the mixed-air temperature should equal the outdoor-air temperature — it doesn't.
Why does it matter?
Either the damper isn't actually open (linkage, actuator), return air is leaking through a closed return damper, or a sensor is wrong — any of which quietly defeats the economizer.
What should you do?
Stroke the OA and RA dampers and watch MAT respond; compare OAT and MAT sensors against a reference; check for a stuck return damper.
This is a diagnostic rule: Energy Agent surfaces and ranks it as a data quality problem and claims no dollar savings for it, by design.