What does AHU-FC11 mean?
The unit is at 100% outdoor air and still running the cooling coil, although the outdoor air alone is colder than the supply setpoint.
Why does it matter?
The economizer should be modulating the damper down instead of paying for chilled water. This is pure waste for as long as it lasts.
What should you do?
Check the economizer changeover and the damper minimum/maximum limits; verify the cooling valve seats; confirm the sequence lets the damper modulate before the coil enables.