AHU-FC12 · Air-side AHU · ASHRAE Guideline 36 FC12

SAT too high relative to MAT in cooling mode

When cooling is active, SAT should drop below MAT.

Capacity-basedBAS trendsGuideline 36Medium effort

What does AHU-FC12 mean?

When cooling is active, SAT should drop below MAT. If SAT is higher than MAT, cooling isn't working.

Why does it matter?

Lost cooling capacity — coil is air-bound, chilled-water flow isn't reaching it, or the valve is reporting open but stuck. Compounds with FC07-type symptoms on the heating side.

What should you do?

Check CHW supply temperature at coil inlet, CHW pump operation, and coil water-side condition. Verify cooling valve actuator linkage.