AHU-FC13 · Air-side AHU · ASHRAE Guideline 36 FC13

Supply air too warm with the cooling valve full open

The cooling coil is doing everything it can and the supply air is still above setpoint.

Capacity-basedBAS trendsGuideline 36Medium effort

What does AHU-FC13 mean?

The cooling coil is doing everything it can and the supply air is still above setpoint.

Why does it matter?

Zones downstream will drift warm and the chilled-water plant is being asked for capacity it can't deliver here — low CHW flow, warm CHW, a fouled coil, or an undersized coil.

What should you do?

Check chilled-water supply temperature and differential pressure at this AHU; look for a closed isolation valve or air-bound coil; clean the coil; compare against the plant's CHW supply setpoint.

How Energy Agent prices a finding

Written by Pelorus Engineering · Brent Waluzak, P.E. (FL), President, Pelorus EngineeringLast updated
Estimate it

What should the economizer be saving?

Estimate the free cooling a working economizer delivers in your climate.

Tampa is 2A; Atlanta 3A; Chicago 5A; Denver 5B; Seattle 4C.
Share of those hours the economizer actually displaces mechanical cooling.
Enter a repair or controls-change cost to see the simple payback.
Avoidable cost per year—Energy —Simple payback Enter a cost to fix to see the payback.

    Cooling capacity, times the hours a year outdoor air can do the job in your climate zone, times an effectiveness factor, priced at your rate. Energy Agent counts the actual hours the coil ran when it did not need to.

    Screening estimate. Energy Agent measures the real fault hours and load from your trends and prices them at your tariff.

    Screening-level estimates; confirm with measurement and verification before capital commitment.

    Your first building is free.

    Send twelve months of interval data, a BAS trend export, or just the bills. You get a screening-level report of what the building is wasting, what that is worth at your tariff, and what to do first. One building per organisation, no sensors, no installation, no commitment.