AHU-X12 · Air-side AHU

Reheat active during unoccupied hours

Hot-water reheat is running at night or on weekends when the building should be unoccupied and unconditioned.

Capacity-basedBAS trendsLow effortNeeds schedule

What does AHU-X12 mean?

Hot-water reheat is running at night or on weekends when the building should be unoccupied and unconditioned.

Why does it matter?

There's no setpoint-defensible reason to reheat empty space. This is a top driver of high winter baseload and is usually a forgotten override or a leaky valve being chased by night setback control.

What should you do?

Check whether night-setback heating is too aggressive, whether a manual override has never been cleared, and whether the valve is mechanically leaking (a closed-command valve at 90°F downstream usually means leak-through).

How Energy Agent prices a finding

Written by Pelorus Engineering · Brent Waluzak, P.E. (FL), President, Pelorus EngineeringLast updated

Screening-level estimates; confirm with measurement and verification before capital commitment.