AHU-X02 · Air-side AHU

Reheat clawing back overcooled air

Zone temperature dropped below setpoint and reheat then activated to recover — the AHU overcooled and is paying to heat back up.

Physics-basedBAS trendsMedium effort

What does AHU-X02 mean?

Zone temperature dropped below setpoint and reheat then activated to recover — the AHU overcooled and is paying to heat back up.

Why does it matter?

Pure double-energy waste — chilled water removed heat that gas then had to put back. Usually rooted in a too-low SAT setpoint or oversized cooling coil.

What should you do?

Raise the SAT setpoint or implement SAT reset based on zone demand. Check whether the zone has a leaking damper or reheat valve causing the initial overcooling.

How Energy Agent prices a finding

Written by Pelorus Engineering · Brent Waluzak, P.E. (FL), President, Pelorus EngineeringLast updated

Screening-level estimates; confirm with measurement and verification before capital commitment.