AHU-X13 · Air-side AHU

Outside-air damper open past minimum without economizer reason

The OA damper is open well past its minimum position even though OAT is too hot or too cold for free cooling to be useful.

Capacity-basedBAS trendsMedium effort

What does AHU-X13 mean?

The OA damper is open well past its minimum position even though OAT is too hot or too cold for free cooling to be useful.

Why does it matter?

Each percent of excess OA is conditioned, dehumidified, and reheated for no ventilation benefit. In peak summer or winter, every CFM of excess OA carries a measurable kWh cost.

What should you do?

Verify the economizer enable logic (high-limit lockout temp). Check whether the damper actuator is sticking open or whether minimum-OA logic has been hard-coded above design ventilation.

See it happen · interactive 3DSwitch AHU-X13 on in the interactive 3D air handlerOpens the air handler on this fault: watch the dampers, the coils, the boxes and the bill change.

How Energy Agent prices a finding

Written by Pelorus Engineering · Brent Waluzak, P.E. (FL), President, Pelorus EngineeringLast updated

Screening-level estimates; confirm with measurement and verification before capital commitment.