ERV-FC16 · Air-side AHU · ASHRAE Guideline 36 ERV-FC16

Energy recovery not recovering

The recovery wheel or core is commanded on but the supply air isn't being pre-conditioned much by the exhaust stream.

Capacity-basedBAS trendsGuideline 36Medium effort

What does ERV-FC16 mean?

The recovery wheel or core is commanded on but the supply air isn't being pre-conditioned much by the exhaust stream.

Why does it matter?

A dead recovery section shifts its whole load onto the heating and cooling coils — often 20–40% of the unit's conditioning energy.

What should you do?

Check the wheel belt/motor and rotation, the bypass damper position, frost-control settings, and whether the wheel is fouled; verify the sensors are on the correct side of the wheel.