ZONE-01 · Zones & IAQ

Over-ventilating a lightly occupied zone

CO₂ is far below the demand-control setpoint while the outdoor-air damper is wide open.

Capacity-basedBAS trendsMedium effortNeeds schedule

What does ZONE-01 mean?

CO₂ is far below the demand-control setpoint while the outdoor-air damper is wide open.

Why does it matter?

Every cubic foot of outdoor air beyond what the occupants need is heated, cooled and dehumidified for nothing.

What should you do?

Enable or fix demand-controlled ventilation; check the CO₂ sensor calibration and the damper minimum.