ZONE-07 · Zones & IAQ

Night setback too shallow

The unoccupied cooling and heating setpoints are within a few degrees of the occupied ones — the zone is kept at comfort conditions overnight and at weekends.

Capacity-basedBAS trendsLow effortNeeds schedule

What does ZONE-07 mean?

The unoccupied cooling and heating setpoints are within a few degrees of the occupied ones — the zone is kept at comfort conditions overnight and at weekends.

Why does it matter?

Unoccupied hours are two-thirds of the week; a 5–10 °F setback typically cuts unoccupied HVAC energy by 20–40 %.

What should you do?

Set unoccupied setpoints to about 80 °F cooling / 60 °F heating with optimal-start recovery, and confirm the occupancy schedule matches how the space is used.