What does PLANT-01 mean?
The chiller is on but CHW supply temperature is above its setpoint by more than the tolerance.
Why does it matter?
Source-side problem: every downstream AHU and VAV will see warm CHW and either ramp valves wide open or fail to control SAT. Many AHU-side faults (FC07, FC12) downstream of this one are actually consequences of it — the suppression layer hides them.
What should you do?
Check refrigerant charge, condenser heat-rejection (cooling tower performance), evaporator approach. Verify CHW pump head and flow. Inspect for fouled tubes.
This is a diagnostic rule: Energy Agent surfaces and ranks it as a reliability problem and claims no dollar savings for it, by design.
See it happen · interactive 3DSwitch PLANT-01 on in the interactive 3D campus plantOpens the plant on this fault: watch the chillers, the mains and a year of plant energy change.How Energy Agent prices a finding