PLANT-07 · Central plant

Chiller short-cycling

The chiller is starting and stopping more frequently than its minimum-runtime safety limit allows.

Capacity-basedBAS trendsMedium effort

What does PLANT-07 mean?

The chiller is starting and stopping more frequently than its minimum-runtime safety limit allows.

Why does it matter?

Short-cycling destroys chiller bearings, reduces compressor life by years, and drops average efficiency. Repeated starts also draw heavy in-rush current that can trip utility demand charges.

What should you do?

Check the chiller's minimum run timer and minimum off timer settings. Investigate whether the chilled-water loop is undersized for the load (no thermal mass) or whether staging logic is hunting between stages.

How Energy Agent prices a finding

Written by Pelorus Engineering · Brent Waluzak, P.E. (FL), President, Pelorus EngineeringLast updated
Estimate it

What is short cycling costing?

Estimate the energy wasted on starts, and remember the wear is the bigger bill.

Enter a repair or controls-change cost to see the simple payback.
Avoidable cost per yearEnergy Simple payback Enter a cost to fix to see the payback.

    Each start costs roughly a couple of minutes of full-load energy before the unit is doing useful work. Extra starts above a sane rate, times that penalty, times the unit size and the affected hours. Energy Agent counts the starts from status trends.

    Screening estimate. Energy Agent measures the real fault hours and load from your trends and prices them at your tariff.

    Screening-level estimates; confirm with measurement and verification before capital commitment.