PLANT-09 · Central plant

Chilled-water supply reset absent

The chilled-water supply setpoint stays flat for weeks while the weather swings.

Capacity-basedBAS trendsMedium effortNeeds schedule

What does PLANT-09 mean?

The chilled-water supply setpoint stays flat for weeks while the weather swings.

Why does it matter?

Every degree of warmer chilled water is ~1.5–2% chiller energy; a fixed setpoint gives that up all year.

What should you do?

Add a supply-temperature reset on OAT or valve position, with a dewpoint low limit.

How Energy Agent prices a finding

Written by Pelorus Engineering · Brent Waluzak, P.E. (FL), President, Pelorus EngineeringLast updated

Screening-level estimates; confirm with measurement and verification before capital commitment.