PLANT-03 · Central plant

Condenser approach drifting up — likely tube fouling

The gap between condenser leaving water temp and refrigerant condensing temp has grown over time when normalized by load.

Capacity-basedBAS trendsMedium effort

What does PLANT-03 mean?

The gap between condenser leaving water temp and refrigerant condensing temp has grown over time when normalized by load.

Why does it matter?

Every 1°F of extra approach typically costs 1–2% in chiller efficiency. Compound across a season and the bill is real. Tube fouling is the most common cause; eddy-current testing is the gold-standard inspection.

What should you do?

Schedule a tube cleaning or brush. Check condenser-water chemistry. Verify CW flow is at design.

How Energy Agent prices a finding

Written by Pelorus Engineering · Brent Waluzak, P.E. (FL), President, Pelorus EngineeringLast updated

Screening-level estimates; confirm with measurement and verification before capital commitment.