What does PLANT-16 mean?
The secondary pump differential-pressure setpoint is flat for weeks.
Why does it matter?
Without a valve-position reset the pumps ride the curve at full ΔP all year — often 20–40% of pump energy.
What should you do?
Implement trim-and-respond ΔP reset on the most-open valve; verify the ΔP sensor location.