What does PLANT-13 mean?
The secondary loop pulls more water than the primary supplies.
Why does it matter?
Return water short-circuits through the decoupler, the building supply temperature rises, and coils starve at peak.
What should you do?
Stage another chiller/primary pump earlier, or reduce secondary pump speed; check the flow meters.