What does PLANT-14 mean? Hot-water return to a condensing boiler is warm enough that the flue gas cannot condense, so the boiler runs as a conventional one.
Why does it matter? Above the dewpoint of the flue gas the boiler runs at 85% instead of 95%; the premium paid for a condensing boiler is lost.
What should you do? Lower the supply-temperature reset, fix the loop ΔT (coil valves, bypasses), and verify the return sensor.
How Energy Agent prices a finding
Written by Pelorus Engineering · Brent Waluzak, P.E. (FL), President, Pelorus Engineering Last updated 2026-09-13
Typical evidence Hot-water return too warm for a condensing boiler to condense, all heating season.
From a synthetic demonstration dataset, not a customer building.
At a glance Data BAS trend export Pricing Capacity-based Effort to fix Medium: usually a controls or mechanical repair Screening-level estimates; confirm with measurement and verification before capital commitment.