VAV-02 · VAV / zone

VAV damper leaking when commanded closed

Damper command is at minimum but measured airflow is well above minimum and the serving fan is running.

Capacity-basedBAS trendsMedium effort

What does VAV-02 mean?

Damper command is at minimum but measured airflow is well above minimum and the serving fan is running.

Why does it matter?

Conditioned air bleeding into a zone that doesn't call for it. Cumulatively a big driver of overcooling and energy waste in shoulder seasons.

What should you do?

Inspect damper seat for debris or warpage. Verify actuator travel reaches full close. Replace if blade-and-frame leakage exceeds spec.

How Energy Agent prices a finding

Written by Pelorus Engineering · Brent Waluzak, P.E. (FL), President, Pelorus EngineeringLast updated

Screening-level estimates; confirm with measurement and verification before capital commitment.