What does VAV-03 mean?
Reheat valve is commanded closed but discharge-air temperature is rising above supply-air temperature.
Why does it matter?
Same waste mechanism as a leaking heating valve at the AHU, but at every zone instead of one central place. The aggregate $ across a building can rival a leaking central coil.
What should you do?
Replace the reheat valve cartridge. Check that the actuator is travelling full close. Inspect the HW supply for over-pressurized branch flow.