What does VAV-05 mean?
Reheat valve has been at 100% but the zone temp is still below the heating setpoint.
Why does it matter?
Lost heating capacity at the box. Often hot-water flow doesn't reach the coil, the coil is fouled, or the box is undersized for current load.
What should you do?
Check HW pressure at the box, verify the local balancing valve isn't closed off, and look for coil air-binding.